TECHNICAL INFORMATION
Table C: Conductors Sized (AWG) for
10% Voltage Drop



Use 10% voltage drop for any “noncritical applications: windlass, cabin lights, etc....

  Current (amps)   10% VOLTAGE DROP AT 12 VOLTS
Length
5
10
15
20
25
30
40
50
60
70
80
90
100
10’
18 18 18 16 16 14 14 12 12 10 10 10 10
15’
18 18 16 14 14 12 12 10 10 8 8 8 8
20’
18 16 14 14 12 12 10 10 8 8 8 6 6
25’
18 16 14 12 12 10 10 8 8 6 6 6 6
30’
18 14 12 12 10 10 8 8 6 6 6 6 4
40’
16 14 12 10 10 8 8 6 6 6 4 4 4
50’
16 12 10 10 8 8 6 6 4 4 4 2 2
60’
14 12 10 8 8 6 6 4 4 2 2 2 2
70’
14 10 8 8 6 6 6 4 2 2 2 2 1
80’
14 10 8 8 6 6 4 4 2 2 2 1 1
90’
12 10 8 6 6 6 4 2 2 2 1 1 0
100’
12 10 8 6 6 4 4 2 2 1 1 0 0
110’
12 8 8 6 6 4 2 2 2 1 0 0 0
120’
12 8 6 6 4 4 2 2 1 1 0 0 2/0
130’
12 8 6 6 4 4 2 2 1 0 0 2/0 2/0
140’
10 8 6 6 4 2 2 1 1 0 2/0 2/0 2/0
150’
10 8 6 4 4 2 2 1 0 0 2/0 2/0 3/0
160’
10 8 6 4 4 2 2 1 0 2/0 2/0 3/0 3/0
170’
10 6 6 4 2 2 2 1 0 2/0 2/0 3/0 3/0


     Current (amps)   10% VOLTAGE DROP AT 32 VOLTS
Length
5
10
15
20
25
30
40
50
60
70
80
90
100
10’
18 18 18 18 18 18 16 16 14 14 14 12 12
15’
18 18 18 18 16 16 14 14 12 12 12 10 10
20’
18 18 18 16 16 14 14 12 12 10 10 10 10
25’
18 18 16 16 14 14 12 12 10 10 10 8 8
30’
18 18 16 14 14 12 12 10 10 8 8 8 8
40’
18 16 14 14 12 12 10 10 8 8 8 6 6
50’
18 16 14 12 12 10 10 8 8 6 6 6 6
60’
18 14 12 12 10 10 8 8 6 6 6 6 4
70’
16 14 12 10 10 8 8 6 6 6 6 4 4
80’
16 14 12 10 10 8 8 6 6 6 4 4 4
90’
16 12 10 10 8 8 6 6 6 4 4 4 2
100’
16 12 10 10 8 8 6 6 4 4 4 2 2
110’
14 12 10 8 8 8 6 6 4 4 2 2 2
120’
14 12 10 8 8 6 6 4 4 2 2 2 2
130’
14 12 10 8 8 6 6 4 4 2 2 2 2
140’
14 10 8 8 6 6 6 4 2 2 2 2 1
150’
14 10 8 8 6 6 4 4 2 2 2 2 1
160’
14 10 8 8 6 6 4 4 2 2 2 1 1
170’
12 10 8 6 6 6 4 2 2 2 2 1 1


ABYC Recommends… “Conductors used for panelboard or switchboard main feeders, bilge blowers, electronic equipment, navigation lights, and other circuits where voltage drop must be kept to a minimum, shall be sized for a voltage drop not to exceed three percent. Conductors used for lighting, other than navigation lights, and other circuits where voltage drop is not critical, shall be sized for a voltage drop not to exceed 10 percent.” 11.16.1.2.7.
     Current (amps)   10% VOLTAGE DROP AT 32 VOLTS
Length
5
10
15
20
25
30
40
50
60
70
80
90
100
10’
18 18 18 18 18 18 18 16 16 14 14 14 14
15’
18 18 18 18 18 18 16 14 14 14 12 12 12
20’
18 18 18 18 16 16 14 14 12 12 12 10 10
25’
18 18 18 16 16 14 14 12 12 10 10 10 10
30’
18 18 18 16 14 14 12 14 10 10 10 10 8
40’
18 18 16 14 14 12 12 10 10 8 8 8 8
50’
18 16 14 14 12 12 10 10 8 8 8 6 6
60’
18 16 14 12 12 10 10 8 8 8 6 6 6
70’
18 14 14 12 10 10 8 8 8 6 6 6 6
80’
18 14 12 12 10 10 8 8 6 6 6 6 4
90’
18 14 12 10 10 10 8 6 6 6 6 4 4
100’
16 14 12 10 10 8 8 6 6 6 4 4 4
110’
16 14 12 10 10 8 8 6 6 6 4 4 4
120’
16 12 10 10 8 8 6 6 6 4 4 4 2
130’
16 12 10 10 8 8 6 6 6 4 4 2 2
140’
14 12 10 8 8 8 6 6 4 4 2 2 2
150’
14 12 10 8 8 6 6 6 4 4 2 2 2
160’
14 12 10 8 8 6 6 4 4 2 2 2 2
170’
14 12 10 8 8 6 6 4 4 2 2 2 2
ANCOR Marine Grade™ Products • (800) 424-WIRE • www.ancorproducts.com